R71- 416 Setup

 

          DIP Switch Positions

 

Switches 1 & 2:

Provides four (4) different frequency settings

 

 

Off/Off = High

On/Off = Med/High

 

 

Off/On = Med/Low  

On/On = Low

 

 

 

Switches 3 & 4:

Provide for four (4) different mode settings

 

 

Off/Off = Pulse-on-Entry* 

On/Off = Pulse-on-Exit*

 

 

Off/On = Presence           

On/On = Fault

 

 

*Applies to relay # 2 only

 

 

 

Switches 5 & 6:

Provide four (4) different Presence lengths. 

 

 

Off/Off = 8 min.       

On/Off = 16 min.

 

 

Off/On = 60 min.    

On/On = Permanent

 

 

 

Switch 7:

Not used

 

 

 

Switch 8:

Provides for Fail-safe or fail-secure operation.

                

 

Off = Fail-safe        

On = Fail-secure*
     *(for power on only)

 

 

 

 

 

 

 

Factory Settings: The R71 is shipped with all switches in the down (OFF) position. This provides for the following settings:

Frequency: 

High

Mode Setting:

Pulse-on-Entry (relay #2)

Presence: 

16 minute (both relays)

Relay #1:

Fail-Safe

Relay #2:

Fail -Secure for power

 

 

R71- 416 Pin Number & Color Code

1

  Relay 2 Com     Blue     

6

  Relay 1 N.C.   White
2

  Relay 2 N.O.     Orange

7   Supply + (Live) Red
3

  Relay 2 N.C.      Yellow  

8   Supply – (Neutral) Black
4

  Relay 1 Com     Green=Gnd.

9   Loop        Brown
5

  Relay 1 N.O.     Violet

10   Loop        Gray
R71- 416 Installation Tips

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Supply the proper voltage.  The Bi-Color LED should be solid GREEN with correct power applied.  Over voltage protection is standard with this product.  In the event of incorrect voltage the Bi-Color LED will come on briefly and fade out without damage to unit.   Check voltage sticker on side of oscillator cover. Reapply correct voltage.
2. Solid Red (Bi-Color) LED indicates a current detect.  Vehicle or metal object in the field of detection.
3. Blinking Red (Bi-Color) LED indicates current fault.  Check loop connections (twisted Gray & Brown) to ensure proper, tight connection to loop.
4. Sensitivity level 4 will be adequate for most situations.  Operate detector at lower sensitivity levels while detecting all desired vehicles.
5. Most applications require using the fail-safe relay #1 providing presence (detector stays in detect as long as vehicle is present over the loop, up to presence time limit).  Relay #1 Normally Open connections are:  Pins 4 & 5, the Green (common) and Violet (N.O.) wires from the wiring harness.  These wires are taken to the terminal strip for your desired function.
6. For a second output (pulse or presence) relay 2 is used.  Commonly the #2 (Orange, N.O.) and #1 (Blue, Common) are used, this will provide a Fail-secure for power output.  When using relay 2 select the proper DIP switch settings for your application.Inductive Loop Detectors / Preformed Inductive Loops

 